RT-FS Water-based acrylic sealant spray
Solution to prevent the spread of fire through the interface between the floor and the translucent structure
Applications and advantages:
•Joints between floor slabs and facade
•Wall and floor junction points
•Points with high deformation rate up to 50%
•High elasticity (up to 50%)
•Halogen, solvent and asbestos free
•Can be sprayed or brushed on
•Excellent adhesion characteristics on various surfaces
•Can be painted over
•Maximum width up to 300 mm
•For inside and outside use

TECHNICAL SPECIFICATIONS
Color Total volume / filling / composition output Fire resistance limit: – for pipeline and air duct penetrations – for cable penetrations Scope of supply Application equipment Setting time Recommended service life Shelf life Manufacturer Country of Origin | Red / Gray 450 ml / 430 ml / 4.9 liters* 240 minutes 180 minutes Composition cartridge, 2 mixers RT-01D dispensing device 35 seconds 30 years 12 months Rock Tech FZC UAE |
*For more information, refer to the TDS
NAME | PCS | ITEM NO. |
---|---|---|
RT-01 two-component fire-fighting thermally expanding composition, 430 ml | 1 | 250053 |
RT-01D dispensing device | 1 | 250050 |
RT-620-M additional spout-mixer | 1 | 250011 |

Pos. | Designation | Name |
---|---|---|
1 | part No. 250050 | RT-01 two-component fire-fighting thermal expanding composition |
2 | part No. 250053 | RT-01D dispensing device |
3 | part No. 250012 | RT-M marking plate Sleeves |
DN, mm | Depth of firestop sealing, mm | Volume, L | Quantity of cartridges, pcs |
---|---|---|---|
50 | 50 | 50 | 50 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
50 | 50 | 50 | 50 |
* The total thickness of the penetration filling with fire protection material must be at least 80 mm for IET60 or 200 mm for IET150 (on either side of the penetration). If the penetration is filled on both sides, the thickness of each part must be at least 40 or 100 mm, respectively * The total cross-sectional area of the cable must not exceed 60% of the penetration area (i.e. RT-01 equals 40% or more of the penetration area). * It is allowed to install the following basic materials in the walls and floors: concrete, brick, gas silicate block, sandwich panel, fireproof gypsum board with the rated limit of fire resistance.

Pos. | Designation | Name |
---|---|---|
1 | part No. 250050 | RT-01 two-component fire-fighting thermal expanding composition |
2 | part No. 250053 | RT-01D dispensing device |
3 | part No. 250012 | RT-M marking plate Sleeves |
DN, mm | Depth of firestop sealing, mm | Volume, L | Quantity of cartridges, pcs |
---|---|---|---|
50 | 50 | 50 | 50 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
50 | 50 | 50 | 50 |
* The total thickness of the penetration filling with fire protection material must be at least 80 mm for IET60 or 200 mm for IET150 (on either side of the penetration). If the penetration is filled on both sides, the thickness of each part must be at least 40 or 100 mm, respectively * The total cross-sectional area of the cable must not exceed 60% of the penetration area (i.e. RT-01 equals 40% or more of the penetration area). * It is allowed to install the following basic materials in the walls and floors: concrete, brick, gas silicate block, sandwich panel, fireproof gypsum board with the rated limit of fire resistance.

Pos. | Designation | Name |
---|---|---|
1 | part No. 250050 | RT-01 two-component fire-fighting thermal expanding composition |
2 | part No. 250053 | RT-01D dispensing device |
3 | part No. 250012 | RT-M marking plate Sleeves |
DN, mm | Depth of firestop sealing, mm | Volume, L | Quantity of cartridges, pcs |
---|---|---|---|
50 | 50 | 50 | 50 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
50 | 50 | 50 | 50 |
* The total thickness of the penetration filling with fire protection material must be at least 80 mm for IET60 or 200 mm for IET150 (on either side of the penetration). If the penetration is filled on both sides, the thickness of each part must be at least 40 or 100 mm, respectively * The total cross-sectional area of the cable must not exceed 60% of the penetration area (i.e. RT-01 equals 40% or more of the penetration area). * It is allowed to install the following basic materials in the walls and floors: concrete, brick, gas silicate block, sandwich panel, fireproof gypsum board with the rated limit of fire resistance.

Pos. | Designation | Name |
---|---|---|
1 | part No. 250050 | RT-01 two-component fire-fighting thermal expanding composition |
2 | part No. 250053 | RT-01D dispensing device |
3 | part No. 250012 | RT-M marking plate Sleeves |
DN, mm | Depth of firestop sealing, mm | Volume, L | Quantity of cartridges, pcs |
---|---|---|---|
50 | 50 | 50 | 50 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
50 | 50 | 50 | 50 |
* The total thickness of the penetration filling with fire protection material must be at least 80 mm for IET60 or 200 mm for IET150 (on either side of the penetration). If the penetration is filled on both sides, the thickness of each part must be at least 40 or 100 mm, respectively * The total cross-sectional area of the cable must not exceed 60% of the penetration area (i.e. RT-01 equals 40% or more of the penetration area). * It is allowed to install the following basic materials in the walls and floors: concrete, brick, gas silicate block, sandwich panel, fireproof gypsum board with the rated limit of fire resistance.

Pos. | Designation | Name |
---|---|---|
1 | part No. 250050 | RT-01 two-component fire-fighting thermal expanding composition |
2 | part No. 250053 | RT-01D dispensing device |
3 | part No. 250012 | RT-M marking plate Sleeves |
DN, mm | Depth of firestop sealing, mm | Volume, L | Quantity of cartridges, pcs |
---|---|---|---|
50 | 50 | 50 | 50 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
80 | 80 | 80 | 80 |
50 | 50 | 50 | 50 |
* The total thickness of the penetration filling with fire protection material must be at least 80 mm for IET60 or 200 mm for IET150 (on either side of the penetration). If the penetration is filled on both sides, the thickness of each part must be at least 40 or 100 mm, respectively * The total cross-sectional area of the cable must not exceed 60% of the penetration area (i.e. RT-01 equals 40% or more of the penetration area). * It is allowed to install the following basic materials in the walls and floors: concrete, brick, gas silicate block, sandwich panel, fireproof gypsum board with the rated limit of fire resistance.